FAULT CURRENT LIMITING TRANSFORMER BY CONTROLLING LEAKAGE REACTANCE (20150327)
Authors :
A. BHANDARE
, VISHAL PATIL, INDRAJIT GURAV
, VAIBHAV KUDITREKAR, AMOL KOTMIRE
Abstracts : The purpose of this paper is to experimentally
prove the ability of AC reactance of a transformer to
automatically limit the short-circuit current and to
adjust the output voltage. This transformer is able to
change its reactance leakage resistance by moving the
U-shaped iron mobile unit. It has three functions of
voltage conversion, limiting the short-circuit current
and voltage regulation. The CLT can limit the shortcircuit
current in the circuit connected to the
secondary winding at a very low level. It consists of an
additional U-shaped core between the members. The
design of the base region so that it bypasses the flow
created by the short-circuit current and limits the
secondary side current. In the event of a malfunction,
an increase in the current in the secondary output
circuit in the increase in the flow in the secondary
winding, it will pass through an additional added base
region. Thus, the current in the secondary winding
does not exceed the rated current. The CLT provides a
deeper current limit and may be more suitable for the
distribution area. A large transformer can be used to
meet the increased demand for a bus without a switch
to increase the reliability of the distribution area.
Pages : 24-27